开始学习第五章。
Section 5 Connecting the Controller and Go
Online
连接控制器,转在线
This
section contains the prerequisites for connecting a controller and
the general procedure for downloading a project to the
controller.
本章包含连接到控制器的先决条件和下载项目到控制器的常规过程。
If you have created a project according to
Section 3, MyDoors Project and then followed the instructions in Section 4,
Hardware Configuration, you can
continue with downloading the application in MyDoors
project to a controller.
如果你按照第三章创建了一个项目,MyDoors项目,按照第四章配置了硬件,你可以继续下载 MyDoors 项目的应用到控制器
If you do not have access to a controller or IO
modules, you can still follow this example by using a SoftController. If you
prefer to run with a SoftController;
jump directly to the subsection, Setting the System
Identity in Control Builder on page 82.
果你无权访问控制器或者IO模板,你依然可以使用softcontroller来遵循本例子。如果你喜欢使用softcontroller,跳过直连小节,82页 Control
Builder的System
Identity 。
Firmware
Upgrade
固件升级
The controller firmware and
Control Builder must be of compatible versions. If
you are unsure,
perform the steps in this section.
控制器固件和Control
Builder必须版本兼容。如果你不确定,执行本节步骤。
Firmware can only be upgraded when the
controller has no application and no previous hardware
configuration. If the controller already has an application and
hardware configuration; you have to first reset the controller to
remove all old applications and configuration
information.
固件仅能在控制器没有应用程序且没有以前的硬件配置才可以进行升级。如果控制器已经有应用程序和硬件配置,你必须先复位控制器,移除所有就得应用和配置信息。
Firmware upgrade can be performed from the
control builder via the Ethernet network (see the Control Builder
Online Help). In case of network failure the serial line upgrade
procedure is always available.
通过以太网(见Control Builder在线帮助)从 control
builder执行固件升级。网络故障情况下,通常使用串口线执行固件升级。
Serial Firmware Upgrade Tool cannot be used for
firmware upgrade of PM891. The firmware upgrade of PM891 can be
done using an SD card or from the Remote System dialog in Control
Builder.
窗口固件升级工具不能用于PM891的固件升级。PM891固件升级可以使用SD卡或者Control
Builder远程系统对话框。
Firmware Upgrade via the Serial Cable
(TK212A)
通过串口电缆(TK212A)升级固件
1. Connect the serial cable between the Control
Builder PC and the controller, as specified in Table 2. For the
type of cable, see Appendix D, Communication Cables.
连接Control
Builder计算机和控制器之间的串口电缆,按照表2的规定。电缆型号见附录D,通讯电缆。
Table 2. Cable connection for the
Controller
表 2.
控制器的连接电缆
|
|
|
|
|
|
|
|
No program capable of blocking the
selected COM port, is to be running during upgrade procedure. This
applies in particular to the MMS Server program.
在升级固件过程中,不会运行任何能够阻止选定的COM端口的程序。这尤其适用于MMS程序。
2. Turn on the
power to the Controller
打开控制器电源
3. Select ABB Start
Menu > ABB Industrial IT 800xA > Engineering > Utilities
> Serial Firmware Upgrade. The dialog as in Figure 42
appears
选择ABB开始菜单> ABB Industrial IT 800xA > Engineering
> Utilities > Serial Firmware
Upgrade.此对话框如图42所示。
Figure 42. The Serial Firmware
Upgrade dialog box
图 42. 串口固件升级对话框
4. Select Settings
> COM Port from the drop-down menu. Make sure the settings
correspond to the physical COM port, on the PC to which your cable
is connected.
从下拉菜单选择Settings > COM
Port,确认设置与电缆所连接的 PC 上的物理 COM 端口相对应。
5. Click Connect
and then press the Init push-button on the Controller until the Run
LED starts to blink. Wait about a minute until a message appears.
If connection was successful, a confirmation text will occur in the
Firmware Version text field (Figure 43).
点击连接,然后按下控制器上面的ini按钮,直到LED灯开始闪烁。等待大约1分钟直到一条消息出现。如果连接成功,固件版本文本字段将出现确认文本(图
43)。
Figure 43. A Firmware version
displayed in the text field.
图 43. 在文本框显示固件版本
In the event of an error message
“Connection failed”, you must check the cables and repeat these
steps again.
出现错误事件消息“Connection
failed”,你必须检查电缆,重复此步骤。
6. Select Firmware
version1 from the drop-down menu and click Upgrade. File
transmission starts to the controller. This operation may takes a
few minutes. A confirmation window opens when the controller is
upgraded, see Figure 44.
从下拉菜单选择固件版本1,点击升级。文件开始传输到控制器。此操作可能持续几分钟。当控制器升级后,打开确认窗口,见图44.
Figure 44. The Serial Firmware
Upgrade window
图 44. 窗口固件升级窗口
7. Click OK
点击OK
8. Click
Exit.
点击退出
9. Press the Init
push-button on the Controller until the Run LED starts to
blink.
按下控制器上的ini按钮直到LED灯闪烁。