ABBAC900F学习笔记318:IEC61131-3编程-SFC编程18

(2023-07-02 09:05:10)
标签:

abb

ac900f

freelance2019sp1

iec61131-3编程

sfc编程

分类: ABBDCS
继续学习Freelance2019SP1xia SFCbiancheng .
9.5 Commissioning the SFC program
SFC程序调试
While commissioning an SFC program, it is possible for the program to be operated using functions similar to those available in an SFC display at an operator station.
当调试SFC程序时,可以使用类似于操作台SFC显示的功能来操作程序。
From commissioning it is thus possible to
因此,从调试开始可以:
  • Switch the SFC program between automatic and manual
  • 切换SFC程序手自动
  • Release or block the SFC program
  • 释放或者阻止SFC程序
  • Display the current state of the step or transition.
  • 显示当前步骤或者套件的状态
  • Execute all active transitions and steps manually once.
  • 手动执行所有活动的条件和步骤一次。
  • Execute steps in manual mode and, in contrast to Freelance operator station, in automatic mode also. The processing of steps or transitions is controlled by the Options setting.
  • 在Freelance操作员站上手动和自动执行步骤。步骤或条件的处理由“选项”设置控制。
  • Change time parameters, such as restart time, repeat time and wait time.
  • 修改时间参数,比如重启时间、重复时间和等待时间
  • Switch steps permanently on or off.
  • 永久打开或者关闭步骤
  • Block or force transitions on a one-time basis.
  • 一次性阻止或强制条件。

ABBAC900F学习笔记318:IEC61131-3编程-SFC编程18
上图为英文版freelance2019SP1的截图,中文版的界面语言u是这个样子,后面的学习练习会遇到。
The individual steps and transitions are displayed depending on their state and the type of action execution in the display area of the SFC program. The section of the display can be moved using the horizontal and vertical scroll bars.
各个步骤和条件根据其状态和操作执行的类型显示在 SFC 程序的显示区域中。可以使用水平和垂直滚动条移动显示部分。
During the processing of a sequential control program, no more than 8 steps may be active simultaneously.
在顺序控制程序的处理过程中,同时激活的步骤不得超过8个。
The background color in the display area depends on the operating mode. In Automatic mode the background is transparent and in Manual mode it is blue. The display of steps and transitions is the same in both modes.
显示区域的背景颜色取决于操作模式。在自动模式下,背景是透明的,在手动模式下,背景是蓝色的。在两种模式下,步骤和条件的显示是相同的。
In contrast to Freelance operator station, it is also possible to change the state of steps and transitions in automatic mode.
与自由职业者操作台相比,还可以在自动模式下更改步骤和条件的状态。
In commissioning, it is not possible to change the structure of the SFC program. This is only possible in configuration.
在调试中,不可能改变SFC程序的结构。这只能在配置中实现。
.Each new load of the SFC program results in a restart with the initial step.
SFC 程序的每个新加载都会导致重新启动初始步骤。 