标签:
杂谈 |
参数表
1.
恢复工厂设定:
- 按 ”MENU”
- 找到参数 620
- 按 ”CHANGE DATA”, 选择
INITIALIZE
- 按 ‘OK’
- 断开电源,等待电源灯熄灭
- 送电
2.
Program parameters in
‘Menu’:
Verify each change with
”OK”
102 马达功率 kW (见马达铭牌)
103 马达电压 V (见马达铭牌)
104 马达频率 Hz (见马达铭牌)
105 马达电流 A (见马达铭牌)
106 马达转速 rpm (见马达铭牌)
128 电机热保护。ETR TRIP 1
201 最小马达频率 Hz (见马达铭牌
– 60%)。杀菌机设为0
202 最高马达频率 in
Hz。输出频率上限。 (见马达铭牌 + 10%至少)
205
最高马达频率参考值。与参数202一样,
207, 208 加减速时间。5.00 sec.
315 4.0 mA
323 继电器输出。VLT 运转
- 按 ”DISPLAY STATUS”
当地启动/停止
用于检查马达转向
1.按 ”MENU”
2.按 STOP/RESET (显示开始闪烁)
3.将002更改为 LOCAL
4.按START启动马达, 按STOP/RESET停机
5.将002更改为REMOTE
6.按START 显示回复为平光)
自动调谐
条件:参数设定已完成,转向正确
1.Press STOP/RESET (display start flashing)
2.Program parameter 002 = LOCAL
107 = ENABLE (RS,XS)
3.Start auto tuning by pressing START button
Auto tuning takes approxiamately 3 - 4 min.
4.When auto tuning is ready, the alarm lamp start flashing on
frequency converter and the display show: AUTO MOTOR ADAPT OK
5.Press STOP/RESET to reset alarm.
6.Restore parameter 002 = REMOTE
7.Press START (display return to steady light)
参数设定
Operation & Display
Load & Motor
References & Limits
001ENGLISH100SPEED OPEN
LOOP200132 Hz CLOCKWISE002
REMOTE101H-CONSTANT TORQUE201Min
马达频率003000.000102马达功率
in kW202Max 马达频率004SETUP
1103马达电压 in V203MIN -
MAX005ACTIVE SETUP104马达频率
in
Hz2040.000006NOCOPY105马达电流
in A205Max motor
reference007UPLOAD ALL
PARAM106Rated motor speed
inRPM206LINEAR0081107ENABLE
(RS,XS)2075.00 s009FREQUENCY
[Hz]108depends on the unit2085.00
s010REFERENCE [%]109depends on
the unit209depends on the
unit011马达电流
[A]110100%210depends on the
unit012POWER [kW]1111.0
Hz211depends on the
unit013LCP+DIG CTRL/ AS
P100112not used212depends on the
unit014DISABLE113100%21310.0
Hz015DISABLE114100%
214SUM016DISABLE115100%2150.00%017ENABLE1160.50
s2160.00%018LOCKED117100%217
0.00%019LOCAL=STOP1185
ms2180.00%1190.0
sec.2190.00%1200.0
sec.220notused121COAST/DELAY
TIME221160%122COAST222160%1230.0
Hz2230.0
A12450%224
IVLT,MAX12550%2250.0
Hz12610.0 sec.226132.0
Hz1270.0 Hz
(OFF)227-4000.000128ETR TRIP
1228
4000.000129NO2290
(OFF)%1300.0 Hz2300.0
Hz1310.0 Volt2310.0
Hz2320.0 Hz2330.0
Hz(Cont’d)
Inputs & OutputsSpecial functionsSerial
communication300RESET400OFF5001301FREEZEREFERENCE401depends
on the unit5019600 BAUD
302START402depends on the
unit502LOGIC
OR303REVERSING403ON503LOGIC
OR304COAST
INVERSE404OFF504LOGIC
OR305JOGGING405MANUAL RESET
505LOGIC OR306SETUP MSB/SPEED
UP4065 sec.506LOGIC
OR307SETUP LSB/SPEED DOWN
407NO FUNCTION507LOGIC
OR308REFERENCE408DISABLE508LOGIC
OR3090.0 Volt409OFF
50910.0 Hz31010.0
Volt410depends on the unit51010.0
Hz311NO OPERATION411depends on
the unit
511not used3120.0
Volt412DISABLE512DANFOSS31310.0
Volt413ON5131
sec.314REFERENCE
4140.000514OFF3154.0
mA4151500.00031620.0
mA416%31710
sec.4170.015318OFF4188
ms319
0-IMAX = 0-20 mA41930 ms3205000
Hz4205.03210-FMAX = 0-20
mA42110 ms3225000
Hz422
20.0 Volt323VLT
RUNNING423parameter 1033240.00
sec.424parameter 1043250.00
sec.425parameter 103326UNIT
READY/REM CTRL426parameter
1043275000 Hz427parameter
10332825000 Hz428
parameter 1043291024429parameter
103430parameter 104431parameter
103432parameter
104433100%4340.02
sec.435not used436not
used437NORMAL438ENABLE439parameter
201
4400.014419999.99 sec.
(OFF4420.00 sec.
(OFF)4435.04440.01445DISABLE446AUTOMATIC
4470%4481.0004490.00%Technical
functions618DO NOT RESET619DO NOT
RESET620NORMAL OPERATION
Note:
Parameter settings in bold italic are specific
for TA FlexD. All other parameter settings are the factory settings
from the manufacturer of the frequency converter (Software version:
3.0x).
For the setting of parameter 102, 103, 104,
105 and 106, 见马达铭牌.
Record all parameters changed from factory
settings settings in test protocol.
Sett following parameters after ready test /
commissioning: Parameter 7 to UPLOAD (save settings in display
EEPROM) Parameter 14 to DISABLE (disable STOP-button on frequency
converter display) Parameter 18 to LOCKED (disable parameter
changes from display)
Save parameter settings to PC by VLT Dialog
software program after test /
commissioning.