Soft start maintenance master wechat ID: ctcr123 simple work 13908182700 engaged in the research and development of motor soft start control algorithm after-sales maintenance for nearly ten years, is committed to the soft start control board drive board maintenance of imported brands for more than 6 years, accumulated countless maintenance cases and experience, basically can do not limit the fault, not to change the board maintenance, there is a fault in this can contact. You can also send emails to consult and exchange. 13908182700@163.com

In the second semester of grade six, the child was a little busy, and there was almost no time to record maintenance. A customer in Shijiazhuang, Hebei Province sent two Siemens soft start, one corner phase fault, one can not start the thyristor temperature is too high. Are used on the compressor of the gas station, the fault is more difficult to get.

Check as follows

Brand: Siemens

Model number: 3RW4445-6BC44

Current :313A

Power: 160KW

Voltage: 400v

Fault phenomenon: start the alarm phase Angle control fault, can not start the motor.

Maintenance idea: The main host SCR is basically normal, the drive board is normal, and most of the faults can be repaired when the control board moves to part.

This fault has been encountered several times before, according to previous experience to repair not done, boot no longer alarm, repeated automatic restart, do not know where there is a problem. Don't be too embarrassed

There are two cases when the phase Angle control error occurs in the 3RW44 soft starter:

1. Possible causes of failure when the motor does not start:

a. Motor connection is incorrect;

b. The internal loop is incorrectly configured.

c. The ground fault occurs.

Solution: Check the cable connection.

2. Possible causes of motor startup failure:

a. The starting voltage is too high.

b. Trip pulse setting error.

Solution: Check parameter Settings and extend buffer time appropriately.

A week later, the problem was finally solved and started normally. It was sent to the site in Shijiazhuang and started normally, and there was no alarm. The fault was repaired successfully.

Siemens soft start need repair and accessories can be contacted ~